Anderson plug cable size calculator

Enter the current your Anderson circuit carries and the one way cable length from battery to plug. The calculator shows how many volts you lose in the cable and the smallest common Australian cable size that keeps the loss under your limit.

CableCopperDropArrives

Formula: drop = 2 × length × amps × 0.0172 ÷ copper area in mm² (copper at 20 °C; expect a little more when the cable is hot). Copper areas are typical figures for Australian cable and vary slightly by maker.

Length means one way

Measure the cable run from the battery to the Anderson plug. The calculator doubles it for you because current flows out on the positive and back on the negative.

6 mm auto cable is not 6 square millimetres

Australian auto cable is named by its outside diameter including insulation. 6 mm auto cable has roughly 4.59 mm² of copper. B&S sizes are much heavier: 8 B&S is about 7.7 mm² and 6 B&S about 13.5 mm². That gap is why a circuit wired in 6 mm auto often underperforms.

What fits a 50 A Anderson plug

Standard SB50 contacts are made for 6 B&S cable. Contacts for 8 B&S and smaller cable are sold separately, so buy the contact that matches your cable instead of packing out a loose crimp.

Voltage drop is not the only limit

The cable also has to carry the current without overheating, and the circuit needs a fuse or breaker close to the battery sized to protect the cable. Check the current rating on the cable you buy.